Slots | |
---|---|
Occupied slots | 1 |
Supply | |
Connection | backplane bus |
Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
Power dissipation | 0.65 W |
Power consumption | 0.65 W |
Internal bus | |
Connection | backplane bus |
Interface | manufacturer-specific bus to standard com unit |
Digital input | |
Number of channels | 1 |
Function | |
Sensor interface | |
Connection | channel I: 1+, 2-; direction: 4+, 5- |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA |
Voltage | 8.2 V |
Internal resistor | 1 k? |
Line fault detection | can be switched on/off for each channel via configuration tool |
Minimum pulse duration | ; in frequency + counter mode: 12.5 ms ; otherwise 20 µs |
Operating frequency | 0 ... 400 Hz ; in frequency + counter mode ... 40 Hz |
Indicators/settings | |
LED indication | Power LED (P) green: supply Status LED (1) red: line fault |
Coding | optional mechanical coding via front socket |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Environmental test | EN 60068-2-14 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Damaging gas | EN 60068-2-42 |
Relative humidity | EN 60068-2-56 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications | |
Degree of protection | IP20 when mounted on backplane |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14...1.5mm2) or screw terminals (0.08...1.5mm2) |
Mass | approx. 90 g |
Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) |
Data for application in connection with hazardous areas | |
Certificate | PF 08 CERT 1234 X |
Galvanic isolation | |
Directive conformity | |
International approvals | |
ATEX approval | PTB 03 ATEX 2042 |
IECEx approval | BVS 09.0037X |